Control Systems
V-84
3
3
Integrated management system
3-1. DMS (Data Management Server)
1) MIM-D00
(1) General description
• Built-in web server
- PC-independent management
- Internet access control
• 16 centralized controllers supported
• Up to 256 indoor units can be controlled individually or in groups
• Schedule control (Weekly, Daily)
• Multiple upper-layer control access (S-NET i, S-NET 3, S-NET mini, PC)
• 2 digital inputs (Emergency/Lock), 2 digital outputs (Operation/Error)
• Current time management even during power failure (for 24 hours)
• Data storage in non-volatile memory
• Emergency stop function with simple contact interface
Name Description
Power supply 100~240VAC (
+
10%), 50/60Hz
Power consumption 5.5W
Operating temperature range 0 °C~ 40 °C
Operating humidity range 0%RH ~ 90%RH
Storage temperature range -20 °C~ 70 °C
Lower layer : RS485 (to centralized controllers)
Communication connection Upper layer : Ethernet 10Base-T
(to S-NET3, S-NET i, S-NET mini, Web Browser)
Max. communication length
Lower layer : Maximum 1000m (RS485)
Upper layer : 100m (for one segment without repeaters)
Max. number of interface
Lower layer : 16 centralized controllers
Upper layer : Unlimited
05-3_control systems(082~141) 3/6/08 14:03 Page 84

Table of Contents

Other manuals for Samsung DVM PLUS III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung DVM PLUS III and is the answer not in the manual?

Samsung DVM PLUS III Specifications

General IconGeneral
BrandSamsung
ModelDVM PLUS III
CategoryAir Conditioner
LanguageEnglish

Related product manuals