As shown in the example, when the combination rate exceeds 100%, the capacity of outdoor unit is
calculated using 100, 110, 120, 130% tables. However, when the combination rate is below 100%, use
capacity presented at the 100% table.
◆ Compact combinations
18HP (Heat Pump / Heat Recovery)
;
NN
NN
oo
oo
tt
tt
ee
ee
Ô Thus, outdoor unit capacity can be calculated as follows:
❺ Using capacity graph of max. piping length and level difference, get the capacity reduction ratio.
- Max. Piping length (outdoor unit to the farthest indoor unit): 60m
- Level difference: -20m
From the above conditions, as the capacity of outdoor unit is 92.2%, its actual capacity is 51.5kW x 92.2% = 47.5kW
(51.5kW: RVXVHT180** 105% combination capacity)
Combination rate of actual indoor and outdoor units= 130% Refer to 130% capacity table
120% < Combination rate of actual indoor and outdoor units < 130%
Calculate with 120% & 130%
capacity table
Combination rate of actual indoor and outdoor units= 120% Refer to 120% capacity table
110% < Combination rate of actual indoor and outdoor units < 120%
Calculate with 110% & 120%
capacity table
Combination rate of actual indoor and outdoor units= 110% Refer to 110% capacity table
100% < Combination rate of actual indoor and outdoor units < 110%
Calculate with 100% & 110%
capacity table
Combination rate of actual indoor and outdoor units < 100% Refer to 100% capacity table