Installation
VI-12
1
1
DVM PLUS III, DVM PLUS III HR
1-5. Electric specifications
1) Basic models
2) High efficiency combinations
8 RVXVHT080GE / RVXVRT080GE 25 25A, 30mA 0.1 Second or less
10 RVXVHT100GE / RVXVRT100GE 30 30A, 30mA 0.1 Second or less
12 RVXVHT120GE / RVXVRT120GE 40 30A, 30mA 0.1 Second or less
14 RVXVHT140GE / RVXVRT140GE 40 40A, 30mA 0.1 Second or less
16 RVXVHT160GE / RVXVRT160GE 50 50A, 30mA 0.1 Second or less
Classification Capacity (HP) Model MCCB (A) ELB
Single unit
RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE
RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE
16 2 50 50A, 30mA 0.1 Second or less
18 1 1 50 50A, 30mA 0.1 Second or less
20 2 60 60A, 100mA 0.1 Second or less
22 1 1 60 60A, 100mA 0.1 Second or less
24 3 75 75A, 100mA 0.1 Second or less
26 2 1 75 75A, 100mA 0.1 Second or less
28 1 2 75 75A, 100mA 0.1 Second or less
30 3 100 100A, 100mA 0.1 Second or less
32 2 1 100 100A, 100mA 0.1 Second or less
34 2 1 100 100A, 100mA 0.1 Second or less
36 1 1 1 100 100A, 100mA 0.1 Second or less
38 1 2 100 100A, 100mA 0.1 Second or less
40 1 2 125 125A, 100mA 0.1 Second or less
42 3 125 125A, 100mA 0.1 Second or less
44 3 1 125 125A, 100mA 0.1 Second or less
46 2 1 1 125 125A, 100mA 0.1 Second or less
48 2 2 125 125A, 100mA 0.1 Second or less
50 1 1 2 150 150A, 100mA 0.1 Second or less
52 2 2 150 150A, 100mA 0.1 Second or less
54 1 3 150 150A, 100mA 0.1 Second or less
56 4 150 150A, 100mA 0.1 Second or less
Module
installation
High
efficiency
combinations
Classification
Basic model
Capacity
(HP)
MCCB
(A)
ELB