I
NSTALLATION
VI-13
RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE
RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE
18 1 1 50 50A, 30mA 0.1 Second or less
20 2 60 60A, 100mA 0.1 Second or less
22 1 1 60 60A, 100mA 0.1 Second or less
24 1 1 75 75A, 100mA 0.1 Second or less
26 1 1 75 75A, 100mA 0.1 Second or less
28 2 75 75A, 100mA 0.1 Second or less
30 1 1 100 100A, 100mA 0.1 Second or less
32 2 100 100A, 100mA 0.1 Second or less
34 1 2 100 100A, 100mA 0.1 Second or less
36 3 100 100A, 100mA 0.1 Second or less
38 2 1 125 125A, 100mA 0.1 Second or less
40 2 1 125 125A, 100mA 0.1 Second or less
42 1 1 1 125 125A, 100mA 0.1 Second or less
44 2 1 125 125A, 100mA 0.1 Second or less
46 1 2 125 125A, 100mA 0.1 Second or less
48 3 125 125A, 100mA 0.1 Second or less
50 3 1 150 150A, 100mA 0.1 Second or less
52 3 1 150 150A, 100mA 0.1 Second or less
54 1 1 2 150 150A, 100mA 0.1 Second or less
56 1 1 2 150 150A, 100mA 0.1 Second or less
58 1 3 150 150A, 100mA 0.1 Second or less
60 1 3 175 175A, 100mA 0.1 Second or less
62 1 3 175 175A, 100mA 0.1 Second or less
64 4 175 175A, 100mA 0.1 Second or less
Module
installation
Compact
combinations
Classification
Basic model
Capacity
(HP)
MCCB
(A)
ELB
◆ All field wiring and components have to comply with local and national codes.
◆ All field wiring work have to be provided by licensed electrician.
◆ When the length of power cable is 50m over, reselect power cable after full consideration of voltage drop.
;
NN
NN
oo
oo
tt
tt
ee
ee
3) Compact combinations
06_Installation(02~45) 3/15/08 4:34 Page 13