Installation
VI-20
1
1
DVM PLUS III, DVM PLUS III HR
Branch with Y-joint Branch with Y and Header joint Branch with Header joint
G
F
hijklmn
b
a
cdefg
p
b
a
cde f
g
h
i
k
j
b
a
cd ef
g
h
i
One outdoor unit
installed
G
F
hijklmn
b
a
cdefg
p
b
a
cde f
g
h
i
k
j
b
a
cd ef
g
h
i
Multiple outdoor
units installed
1-7. Refrigerant piping works
3) Piping examples
DVM PLUS III
Branch with Y-joint a+b+c+d+e+f+g+p 200 m(220 m)
Branch with Y-joint and a+i+k 200 m (220 m)
Header joint a+b+h 200 m (220 m)
Branch with header joint a+i 200 m (220 m)
Branch with Y-joint
a+b+c+d+e+f+g+p+h+i+j+k+l+m+n 1000 m
Branch with Y-joint and
a+b+c+d+e+f+g+p+h+i+j+k 1000 m
Header joint
Branch with
Header joint
a+b+c+d+e+f+g+p+h+i 1000 m
Outdoor ~ Outdoor unit
Piping 10 m below r 10, s 10, t 10 m
Equivalent piping 13 m below r 13, s 13, t 13 m
Outdoor ~ Indoor unit Piping 50 m / 40 m*
2)
H1 50/40 m
Indoor ~ Indoor unit Piping 15m below H2 15 m
Outdoor ~ Outdoor unit Piping 5m below H3 5 m
Piping
45m below b+c+d+e+f+g+p 45 m, i 45 m
90m below *
1)
It needs to satisfy required conditions
Equivalent pipe length
Y-joint : 0.5 m, Header : 1 m
Elbows : Refer to the
page VI-23.
Only apply to DVM PLUS III
(DVM PLUS III HR exclusion)
Max.
piping
length
Items Examples Remarks
Level
difference
The first branch
~
the farthest Indoor unit
Allowable
length after
branch
Outdoor ~ Indoor unit
Piping
(Equivalent piping)
200 m below
(220 m below)
Total piping 1000 m below
Allowable
From distribution kit to indoor unit 3 m MEV-A13SA / MEV-A16SA ( For 1 indoor unit)
From distribution kit to indoor unit 20 m
MXD-A13K116A / MXD-A13K200A / MXD-A16K200A / MXD-A22K200A ( For 2 indoor units)
MXD-A13K216A / MXD-A13K300A / MXD-A16K213A / MXD-A16K300A ( For 3 indoor units)
For wall-mounted &
ceiling indoor unit
Distribution Kit Model Remarks
If the sum of pipe length (b+c+d+e+f+g+p) is over 45m,(but not exceed : 90m)
Increase pipe size of b, c, d, e, f, g. (b, c, d, e, f, g : pipe 1 size up)
If main pipe size is not increased,
a+bx2+cx2+dx2+ex2+fx2+gx2+h+i+j+k+l+m+n+p 1000 m
If main pipe size is increased,
ax2+bx2+cx2+dx2+ex2+fx2+gx2+h+i+j+k+l+m+n+p 1000 m
h, i, j,...p 45 m
The difference between the distance of the outdoor unit to the farthest indoor
unit and the distance of the outdoor unit to the nearest indoor unit 45m
(a+b+c+d+e+f+g+p) - (a+h) 45m
Required condition Example
*2) As an outdoor unit is located in a lower position than indoor unit, level difference is 40m.
The refrigerant amount of the system must be less than 100kg. For more detail, refer to the page VI-24.
*1) Required condition
The first branch joint ~
the farthest indoor unit
Total pipe length
Each Y-joint ~each indoor
Between indoor units
G
F
hijklmn
b
a
cdefg
p
06_Installation(02~45) 3/15/08 4:34 Page 20

Table of Contents

Other manuals for Samsung DVM PLUS III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung DVM PLUS III and is the answer not in the manual?

Samsung DVM PLUS III Specifications

General IconGeneral
BrandSamsung
ModelDVM PLUS III
CategoryAir Conditioner
LanguageEnglish

Related product manuals