Control Systems
V-96
3
3
Integrated management system
3-1. DMS (Data Management Server)
Setup for power distribution
This setting is mostly used for the case that electricity billing rates differ in time section of day.
S-NET3 must be used together to support time section setting for power distribution.
Segmented tables for different rate sections are seen on the S-NET3 screen to enter time-dependent billing rates.
Environment setup for power distribution
This setting is the most important and attention-requiring task to make reasonable power distribution on the basis
that consumed power in one indoor/outdoor system is distributed to all indoor units in that boundary.
Indoor unit address
Ex) 00.00.00
Watt-hour meter address for
outdoor unit power supply
Centralized controller address
Interface module address
Indoor unit MAIN address
Watt-hour meter address for
indoor unit power supply
◆
If watt-hour meters are left unmapped to the designated indoor/outdoor units, power distribution is not functioned.
But, power distribution ratio is stored and can be used for later power distribution.
When watt-hour meters are mapped to the wrong indoor/outdoor units, it also results in incorrect power distribution. In
this case, it needs bothersome manual calculation to recover correct result.