LED R&D Lab(VD)
20
• Flow calculation and FAN selection example
– Select model and screen configuration from the following site
https://displaysolutions.samsung.com/support/tools/led-configurator
– PDF download after login
– If the flow rate is indicated, it is necessary to install a fan and air conditioner.
※ FAN flow is not MAX but actual flow, so sufficient margin is required
– Ebm papst : http://www.ebmpapst.com
Example size : 60*60*32
Example flow : MAX 48.3 CFM Installation quantity: 3ea per row
– delta-fan : http://www.delta-fan.com
Example size : 60*60*38
Example flow : MAX 54.5 CFM Installation quantity: 3ea per row
Outside
air
30℃
5 Cabinets
Total flow 400 CFM
80 CFM 80 CFM 80 CFM 80 CFM80 CFM
FAN
5 Cabinets
Select
MODEL / SCREEN
※ Fan margin required for pressure drop/flow reduction
※ Fan margin required for pressure drop/flow reduction
1. Product Information and Installation Precautions