126 S&C Instruction Sheet 461-504
Appendix B
Screen Name Description
Remaining Contact
Wear in %
The remaining vacuum interrupter contact wear, in percent, is displayed.
LCD Screen
Temperature
The temperature of the LCD screen shortly before the recloser loses power, in Celsius degrees, is
displayed.
TCC #0 (Initial Trip) The short name for the Initial Trip curve is displayed.
TCC #1 (Test 1) The short name for the Test 1 curve (2nd TCC curve) is displayed. If the Test 1 operation is
disabled but this screen is selected, the Normal screen will be displayed instead.
TCC #2 (Test 2) The short name for the Test 2 curve (3rd TCC curve) is displayed. If the Test 2 operation is
disabled but this screen is selected, the Normal screen will be displayed instead.
TCC #3 (Test 3) The short name for the Test 3 curve (4th TCC curve) is displayed. If the Test 3 operation is
disabled but this screen is selected, the Normal screen will be displayed instead.
Sectionalizing Mode
Counts
The number of counts for Sectionalizing mode is displayed. If Sectionalizing mode is disabled
but this screen is selected, the Normal screen will be displayed instead.
Interrupting Rating The interrupter rating of the recloser in kA is displayed.
Max Rated Voltage The rated max voltage of the recloser: either 15.5 kV or 29.0 kV is displayed.
System Frequency The frequency in Hz, of the electrical system the TripSaver II recloser is configured for, is
displayed.
Software Versions Three pieces of information about software version are displayed: Application; Bootloader; and
Radio Frequency MicroController Unit.