S&C Instruction Sheet 461-504 101
Informational and Settings Screens
Operation Count (X). Enter an integer to specify the LMO trigger condition
(minimum value: 6; maximum value: 16).
Operation Time Window, s (Y). Enter an integer to specify the time window within
which the LMO command sequence must be completed or it will expire (minimum
value: 30; maximum value: 180; increment: 10).
Disabling LMO. “0” is accepted as a valid entry for both of these two user-congu-
rable elds. The LMO function can be disabled by setting either or both values to “0”.
The factory default setting for the Standalone (ofine) mode is the Disabled state, with
both elds set to “0.” All TripSaver II reclosers will leave S&C factory with the LMO feature
disabled unless specied otherwise via S&C optional factory programming.
The Communication Settings screen is where the TripSaver II recloser’s
Communication mode and where the Side-Magnet Radio Enabling function are
congured. See Figure 142.
Communication
Settings Screen
Figure 142. The Communication Settings screen.
Communication Mode
The Communication mode is used to enable or disable a TripSaver II recloser with
the Extended Open Interval option’s (Option “-O”) ability to communicate with a
TripSaver® II Communications Gateway. When connected to a TripSaver II recloser,
select the desired Communication mode–either the Gateway Mode or Non-Gateway
Mode setting—from the drop-down menu and click the Apply button on the menu bar
or the Apply Communication Mode button. See Figure 143.
Figure 143. The Communication Mode option menu.