88 S&C Instruction Sheet 461-504
Informational and Settings Screens
Firmware
TripSaver II DSP Application. This indicates the version of the DSP îrmware the
connected TripSaver II recloser is using. See Figure 121 on page 86.
TripSaver II Boot Loader. This indicates the version of the Boot Loader the connected
TripSaver II recloser is using.
TripSaver II Transceiver Application. This indicates the version of the 802.15.4
Transceiver Application Code the connected TripSaver II recloser is using.
USB Transceiver Application. This indicates the version of the 802.15.4 Transceiver
Application Code the USB Transceiver is using.
The Event Logs screen provides eight different historical counts, including the number of
interrupter operations and recloser drop-opens, of the connected TripSaver II recloser,
and the duration and current level of the last 25 trip events. See Figure 123.
Event Logs Screen
Figure 123. The Event Logs screen.
Historical Counts
Number of Forced Interrupter Closes. This is the number of times the vacuum inter-
rupter has been manually reset using the Service Center Conîguration Kit power module,
cordless power module, or a 9-Volt Lithium L522 battery.
Number of Interrupter Open Operations due to Overcurrent. This is the number of
times the vacuum interrupter contacts have opened because of an overcurrent condition.
Total Number of Interrupter Open Operations. This is the total number of times the
vacuum interrupter contacts have opened.