66 S&C Instruction Sheet 461-504
Informational and Settings Screens
Denite Time 2 Time, s. Specify the time delay (in seconds) after which the Denite Time
2 element trips (minimum value: 0; maximum value: 1,000; precision to 10 decimal places)
See Figure 91 on page 65. Note: This value must be less than the DeniteTime setting.
Denite Time 3 (check box). Select this check box to enable the Denite Time 3
element. Note: This eld is not active unless the Denite Time 2 element is enabled.
Denite Time 3 Current, A. Specify current (in primary amperes) at which the Denite
Time3 element picks up (minimum value: 5; maximum value: 6,300). Note: This value
must be greater than the Denite Time 2 Current setting, less than or equal to the
interrupting rating of the recloser, and smaller than the High Current Cutoff setting.
Definite Time 3 Time, s. Specify the time delay (in seconds) after which the
Denite Time3element trips (minimum value: 0; maximum value: 1,000; precision to
10 decimal places). Note: This value must be less than Definite Time 2
setting time.
Note: When changing the selection for Inverse Segment setting at any time, all set-
tings entered for that trip operation except the Emulated Device setting will be erased.
Selecting a Fuse Link Curve
The following describes how to select the fuse link curve:
Emulated Device. Select the Fuse Link option from the Emulated Device pull-down
menu. See Figure 92.
Figure 92. The Fuse Link option.
A new Speed eld and an Ampere Rating eld will open. See Figure 93.
Figure 93. The Speed and Ampere Rating fields.
Speed. Select the fuse link speed from the list in the Speed pull-down menu. See
Figure 94.
Figure 94. The Speed pull-down menu.