66 S&C Instruction Sheet 461-504
Informational and Settings Screens
Denite Time 2 Time, s. Specify the time delay (in seconds) after which the Denite Time
2 element trips (minimum value: 0; maximum value: 1,000; precision to 10 decimal places)
See Figure 91 on page 65. Note: This value must be less than the DeniteTime setting.
Denite Time 3 (check box). Select this check box to enable the Denite Time 3
element. Note: This eld is not active unless the Denite Time 2 element is enabled.
Denite Time 3 Current, A. Specify current (in primary amperes) at which the Denite
Time3 element picks up (minimum value: 5; maximum value: 6,300). Note: This value
must be greater than the Denite Time 2 Current setting, less than or equal to the
interrupting rating of the recloser, and smaller than the High Current Cutoff setting.
Definite Time 3 Time, s. Specify the time delay (in seconds) after which the
Denite Time3element trips (minimum value: 0; maximum value: 1,000; precision to
10 decimal places). Note: This value must be less than Definite Time 2
setting time.
Note: When changing the selection for Inverse Segment setting at any time, all set-
tings entered for that trip operation except the Emulated Device setting will be erased.
Selecting a Fuse Link Curve
The following describes how to select the fuse link curve:
Emulated Device. Select the Fuse Link option from the Emulated Device pull-down
menu. See Figure 92.
Figure 92. The Fuse Link option.
A new Speed eld and an Ampere Rating eld will open. See Figure 93.
Figure 93. The Speed and Ampere Rating fields.
Speed. Select the fuse link speed from the list in the Speed pull-down menu. See
Figure 94.
Figure 94. The Speed pull-down menu.