S&C Instruction Sheet 461-504 83
Informational and Settings Screens
Photo. Depending on the TripSaver II recloser, a photo of either a 15-kV (15.5-kV max) or
25-kV (29-kV max) recloser will be displayed. If a TripSaver II recloser is furnished with
the Extended Open Interval option (“-O”), a black and white clock face icon indicat-
ing “30s” will be displayed on the top right side in the photo frame. See Figure 116 on
page 82 and Figure 118.
15 kV 25 kV
Figure 118. Photos of 15-kV and 25-kV TripSaver II reclosers.
Current, A. This is the instantaneous magnitude of the current owing through the
control, in primary amperes. It’s located below the photo. Current displayed will typically be
0 A~1 A when the TripSaver II recloser is being powered by the power module during
conguration. See Figure 116 on page 82.
Interrupter Contacts. This indicates whether the vacuum interrupter contacts of the
connected TripSaver II recloser are presently open or closed. Note: During a functional
test, it is normal for the vacuum interrupter contacts to show “Transit,” which means the
interrupter contacts are opening or closing.
Mode. This indicates the operational mode of the TripSaver II recloser: AUTO (lever up),
NR (lever down), or R-NR (lever up). In Auto mode, a TripSaver II recloser will perform
open or reclose operations according to the pre-selected TCC curves. In NR (Non-Reclose)
and R-NR (Remote-Non-Reclose) mode, a TripSaver II recloser will not reclose; it will
trip once on the applicable user-specied NR curve or the default instantaneous curve if
the NR curve settings have not been congured (the minimum trip current comes from
the initial trip curve) and then drop open. The TripSaver II recloser automatically resets
approximately 2 seconds after it drops open.
Sectionalizing Mode. This indicates whether the Sectionalizing feature is presently
enabled or disabled in the connected TripSaver II recloser.
Sectionalizing Counts. This indicates the number of source-side circuit breaker or
recloser tripping operations the enabled Sectionalizing feature counts up to before com-
manding a TripSaver II recloser to drop open. The eld is grayed out if the Sectionalizing
feature is disabled.
Battery Charge Level. This eld is only displayed if a recloser is furnished with the
Extended Open Interval option (“-O”). It indicates the battery state of charge, in percent.
The battery state of charge is also represented by a blue “Battery Charge Level” bar at
the bottom of the screen, similar to the “Main Cap Charge” bar.
Battery Status. This eld is only displayed if a recloser is furnished with the Extended
Open Interval option (“-O”). It indicates the status of the battery that is used to support
the extended open interval.
OK: The battery is functioning normally.
Error: This indicates a battery problem.