Saia-Burgess Controls AG
Hardware manual for PCD3 series │ Document 26-789 ENG19│ 2018-06-29
PCD3 CPUs
PCD3.Mxxx0 Classic CPU and expansion enclosure
3-11
3
basic devices
Basic Extended
DP
Master
2 ×
Ethernet
PCD3.M 3160 3360 5360 5560 6560 6860
Serial data interface
Port 2
RS-485, to 115 kBit/s
Port 2
to
187.5 kBit/s
Port 10
to
1.5 MBit/s
Port 10
to
12 MBit/s
Port 2
to
187.5 kBit/s
Ether S-Net interface -
Fieldbus connections
Serial S-Net
Ether-S-Net (TCP/IP) -
1) When using digital I/O modules PCD3.E16x or PCD3.A46x with 16 I/Os each
2) The address 255 is reserved for the watchdog on all PCD3. The I/O reserved for the watchdog can not be
used by the user, and analog and H modules must not be deployed with the slots with base address 240
3) Typical values, the processing time depends on the load on the communication interfaces
4) Thespecieddurationisabuertime,itdependsontheambienttemperature(ahighertemperaturemeans
ashorterbuertime)
5) The 1 kHz apply to a pulse/pause ratio of 1:1 and refer to the sum of the frequencies of the two inputs
6) The USB port is of type USB 1.1 Slave Device 12 MBit/s and can only be used for programming and together
with certain software products (Web-Connect, ViSi.Plus with S-Driver) as S-Bus Slave. The download works twice
as fast with a USB 2.0 hub
Can also be used as serial data interface e.g. used for connecting a terminal, however, this makes the commis-
sioninganddebuggingwiththedebuggerdicult.