Parameters
BV-H2464GB, 1234
- 66 -
INTECONT® Tersus Belt weigher, Instruction Manual
Schenck Process Group
P02.08 Pulse Length Total
Default: 0 ms
Min: 0 ms Max: 10000 ms
Duration of an external totalizing counter output impulse.
The weighting of an impulse is defined by P02.12 Totalizer Increment
If the impulse duration is shorter than 10 ms the impulse output is disabled. All impulses not
issued yet are cleared.
At Nominal Flow Rate the output frequency f is:
f [Hz] = P02.02 / 3600 * Zmin
Zmin = Smallest display unit of counter 1 in kg or t (see P02.07 Counter 1 Unit)
The output frequency must be ≤ 10 Hz if an external counter is connected.
P02.09 Counter 2 Unit
Default: ------- t
Alternative: ------- kg
-----.- kg
----.-- kg
---.--- kg
------- t
-----.- t
----.-- t
---.--- t
Display format for counter 2
P02.10 Counter 3 Unit
Default: ------- t
Alternative: ------- kg
-----.- kg
----.-- kg
---.--- kg
------- t
-----.- t
----.-- t
---.--- t
Display format for counter 3.
P02.11 DO: Pulse Counter
Default: n/a
Alternative: n/a
DO
Select the physical output to control an external impulse counter for the measured quantity.
Bear in mind the limitations on speed and life cycle when selecting a relay output and set
the weight equivalent for an impulse in P02.12 Totalizer Increment. The duration of the
impulse is set by P02.08 Pulse Length Total.