Installation and Commissioning VC 1100
Version 2 → mounting/VC1100E
6-2 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, November 97
Checks
Use the VIBROCONTROL 1100 service functions to verify all
connected peripheral functions.
Service functions are described in chapter 5, under setup para-
meters group S.
Relays: Service parameters S01...S04
Analog outputs: Service parameters S05...S08
These functions provide a means to switch each relay separately
and to set the analog outputs to predefined values.
Complete the installation by running self-test (S09) and auto-
calibration (S10).
Recommendation
Run auto-calibration under operating conditions with the machi-
nery running.
The auto-calibration function does not change setup parameters.