List of Setup Parameters VC 1100
Version 2 → parqalist/VC1100E
5-34 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98
O 03 Channel A : OK-Lower Limit
Choises : -23 V ... + 23 V
Function : The OK-limits are only settable for acceleration
pickups.
O 04 Channel B : OK- Lower Limit
Choises : -23 V ... + 23 V
Function : The OK-limits are only settable for acceleration
pickups.
O 05 Channel A : OK-Upper Limit
Choises : -23 V ... + 23 V
Function : The OK-limits are only settable for acceleration
pickups.
O 06 Channel B : OK- Upper Limit
Choises : -23 V ... + 23 V
Function : The OK-limits are only settable for acceleration
pickups.
Note for the definition of the OK-limits
If the input value of the OK-upper value is smaller than the input
value for the OK-lower value, an OK error message is displayed.
The typical setting values for the OK-upper limit and the OK-lower
limit are dependent on the transducer type. For SCHENCK trans-
ducers the following settings are recommended:
Velocity transducer (series VS - ...)
OK-upper limit : 2.5
OK-lower limit : 0.5
Acceleration sensor (series AS - ...)
OK-upper limit : - 1
OK-lower limit : -20