VC 1100 List of Setup Parameters
VC1100E/paralist Version 2 →
© Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98 C01 / C02 - C11 / C12 5-21
Limit Value Configuration Group M
General
This parameter group enables or disables the monitoring functions
for both channels. Three limit values can be defined for each
channel; two for vibration levels and one for bearing condition.
Each limit value can be enabled or disabled and it's value and
alarm delay time set individually.
The manual uses notations lim_1 (limit 1), lim_2 (limit 2), and
lim_b (BCU) for the limit values. The unit of the corresponding
measured parameter defines the unit of the limit value.
VIBROCONTROL 1100 accepts limit values in the range of 10 %
to 100 % of the corresponding full scale. The consistency check
generates error-message -63 if the limit values are outside this
range.
Alarm delay times are in seconds. If the measured value exceeds
the limit value for a time longer than the alarm delay time, VIBRO-
CONTROL 1100 generates an event. The event is stored in the
Log Book and the assigned relay is tripped as defined in the setup.
Warning:
When an OK error occurs, all limit relays maintain their current
status. After removing the OK error and acknowledging it by "Relay
reset", they perform their normal function again.
Fig. 5 - 6 : Parameter Group M, Limit Value Configuration