VC 1100 List of Setup Parameters
VC1100E/paralist Version 2
© Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98 C01 / C02 - C11 / C12 5-33
OK-Monitoring Group O
General
VIBROCONTROL 1100 has a cyclic self-monitoring routine.
This routine tests the pickups and the cables between VIBRO-
CONTROL 1100 and the pickups. The pickup signal is checked to
verify that it remains within a predefined range. This method de-
tects errors such as disconnected pickups, broken cables and
shorts. If an OK error occurs, the OK relay is tripped and the event
is stored in the Log Book.
Note:
When vibration velocity transducers with moving coil are used,
lead breakage or short-circuit cannot usually be recognized. A
constant current is thus superposed to the measuring signal. This
current effects a direct voltage drop of approx. 1 V in the VC-1100.
This voltage drop is measured as OK voltage.
The OK relay is configured to the normally energized mode. In this
mode a power failure at the VIBROCONTROL 1100 will trip the
OK relay to the alarm position.
In special cases, for example if line drivers or isolation amplifiers
are used, it might be necessary to disable the OK monitoring
function for the pickups. Therefore, VIBROCONTROL 1100 provi-
des for disabling this function. This has no effect on other self-
monitoring functions.
O 01 Channel A : OK Monitoring
Choises : Y, N
Function : Enable or disable OK monitoring of the pickup on
channel A.
Y = OK monitoring for pickup channel A is active
N = OK monitoring for pickup channel A is not
active
O 02 Channel B : OK Monitoring
Choises : Y, N
Function : Enable or disable OK monitoring of the pickup on
channel B.
Y = OK monitoring for pickup channel B is active
N = OK monitoring for pickup channel B is not
active