Overview VC 1100
Version 2 → overview//VC1100E
1-10 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, November 97
Log Book
All events are stored in a circular buffer using short notation. This
buffer can store up to 99 events.
Events are:
Power Up; limit value exceedance; reset instructions; and internal
errors detected by the self monitoring.
If the Log Book capacity is exceeded, the "oldest" event is deleted
and all stored events are shifted one position, freeing space to
store the new event.
The Log Book can be displayed on the built-in display or read via
the remote interface.
Each Log Book entry begins with an "H", (for History) followed by a
two digit running number and a 'short' notation of the event.
Example:
H03 K1 Lim1 A
Meaning:
H03 Label of Log Book entry
K1 Relay K1 tripped
Lim1 A because limit value lim_1 of channel A has been
exceeded.
The Log Book is deleted every time the VIBROCONTROL 1100 is
powered up. It can also be deleted using the built-in operator panel
or via the serial interface.