Connectors and Interfaces VC 1100
Version 2 → connect/VC1100E
3-10 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, November 97
Buffered Outputs
The buffered outputs provide the pickup signals for on site analy-
sis or data collection. The signal is attenuated by a factor of 0.1.
The buffer amplifier strips off the DC part of the pickup signal.
Max. output current Imax : 4 mA
Ohmic load R
L
: > 10 kΩ
Max. cable length with cable capacity
of 70 pF/m (Wire against wire) : ≤ 16 m
Fig. 3 - 8: Connecting to the Buffered Outputs
for On Site Analysis