Self-calibration
The self-calibration program takes about 15 minutes. During this
time, the signal conditioners, multiplexers, and analog-to-digital
converters, etc. are checked using an internally generated test si-
gnal.
This program does not have access to the input and output mo-
dules like relays, pre-amplifiers, and amplifiers for the analog out-
puts. Use the relay and analog output tests to check these functi-
ons.
"Calibration" is displayed during the self-calibration along with a
number indicating the current test. This program is not interrupti-
ble. Remember that during self-calibration all measuring and mo-
nitoring functions are suspended.
The status of the relays and analog outputs does not change du-
ring the self-calibration.
S 01 Relay K1 : Test
Choises : K1 on, K1 off
Funktion : Test relay K1.
K1 on = Relay K1 is active
K1 off = Relay K1 is not active.
S 02 Relay K2 : Test
Choises : K2 on, K2 off
Funktion : Test relay K2.
K2 on = Relay K2 is active
K2 off = Relay K2 is not active abgefallen.
S 03 Relay K3 : Test
Choises : K3 on, K3 off
Funktion : Test relay K3.
K3 on = Relay K3 is active
K2 off = Relay K3 is not active abgefallen.
S 04 OK-Relay : Test
Choises : OK on, OK off
Funktion : Test OK-relay.
OK on = OK-Relay is active
OK off = OK-Relay is not active