VC 1100 List of Setup Parameters
VC1100E/paralist Version 2 →
© Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98 C01 / C02 - C11 / C12 5-37
Service Functions Gruppe S
General
VIBROCONTROL 1100 provides direct access to the relays and
analog outputs. Use these functions to test the connected periphe-
rals including wiring.
These functions also help programmers of process control sy-
stems to verify the interface with VIBROCONTROL 1100. Additio-
nally, VIBROCONTROL 1100 itself can be tested using the self-
test and self-calibration functions.
Warning
The service functions suspend all measuring and monitoring
functions.
Changing relay outputs could cause machine shutdown !
Relay Test
Switch each relay to the "active" and "inactive" position . Test the
reaction of the system in both positions. Repeat the procedure for
all relays including the OK- relay.
Analog Output Test
Set each analog output to a predefined output voltage or current.
Check to see if the same levels are displayed, for example on the
analog meter in the control room.
Self-test
The self-test takes about 15 seconds. During this test the most im-
portant modules of the microprocessor system are checked, inclu-
ding stored data. "Test" is displayed during the test along with a
countdown from 10 to 0. The self-test is not interruptible.
Normally, "TEST ok" is displayed at the end of the self-test. Press
any key to continue.
If the self-test detects an error, the error message is displayed for
x seconds and automati- cally restarts the system.
The error message is stored in the Log Book.