VC 1100 Overview
VC1100E/overview Version 2 →
© Schenck VIBRO GmbH, D-64273 Darmstadt, November 97 C01 / C02 - C11 / C12 1-11
Relays
Three relays are provided which are activated on alarm exceedan-
ce if so programmed.
They are designated as K1, K2, and K3.
Programming the Relays
Relay operation is defined by the setup parameters:
1. Which limit value controls which relay.
2. Latching or Non-Latching Mode.
3. Energized or de-energized Operation.
4. Control a relay by combining several limit values using a
logical OR or AND statement.
Comment to 1.
Limit value exceedances can be configured as single events or
grouped events.
A configuration that is commonly used is, lim_1A and lim_1B con-
trol relay K1, and lim_2A and lim_2B control relay K2.
Comment to 2.
Latching Mode
The relay remains latched (tripped) until it is reset using the control
panel, reset switch, or via the remote interface.
Non-Latching Mode
The relay is automatically reset when the measured value drops
below the limit value.
Comment to 3.
This choice depends on the user's philosophy. What is important
though, is preventing a false relay trip if power to the VIBROCON-
TROL 1100 is disconnected.
Mode No Alarm Alarm
Normally Energized
Normally De-Energized
Relay active
Relay not active
Relay not active
Relay active