Connectors and Interfaces VC 1100
Version 2 → connect/VC1100E
3-4 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, November 97
Inputs
Power Supply
Version Supply Voltage
VC 1100 C01/C11 230 V AC or 115 V AC
VC 1100 C02/C12 24 V DC
115 V AC Wiring 230 V AC Wiring
24 V DC Wiring
Fig. 3 - 2 : Supply Voltage Wiring
Coded Terminal strip 19 - 24 cannot be plugged into any other slot
but its own.
Grounding
Connect protective ground of the power cord to the PE terminal
located on top of the internal housing.
This is the central grounding point for the housing. This point (PE)
is connected to TE by a jumper wire between terminal strip 1/2 and
SE. This is the standard configuration.
In special cases, for example if a peripheral instrument is used
with internally grounded inputs, open the connection between PE
and TE by removing this jumper wire.
Please consult the General Grounding Recommendation in this
manual.