EasyManua.ls Logo

Schenck Vibrocontrol 110 C01 - Outputs; Relays

Schenck Vibrocontrol 110 C01
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VC 1100 Connectors and Interfaces
VC1100E/connect Version 2
© Schenck VIBRO GmbH, D-64273 Darmstadt, November 97 C01 / C02 - C11 / C12 3-7
Outputs
Relays
Consider the following if the relay outputs are to be used.
Decide if the relays are to be "normally energized" or "nor-
mally de-energized". Setup parameters (N10, N11, N12)
must be consistent with the wiring.
Refer to the examples on the next page.
If a relay is configured as latching (see parameters N07, N08,
N09) there are three ways to reset it.
With the operating panel; via the remote interface; using the
Relay-Reset Input
To use the Relay-Reset Input, connect a galvanically free
switch to terminals 35 and 36 (see previous page).
If conductive loads are connected, provide appropriate spark
suppression placed as close as possible to the part that would
generate the spark.
Contact Rating: max. 5 A, 220 V AC (Ohmic load)
A spark extinguisher must be installed as close to the
spark generator as possible !
Fig. 3 - 5 : Connecting the-Relays
Figure 3 - 5 shows the contacts in the de-energized position.

Table of Contents