Technical Data VC 1100
Version 2 → tedata/VC1100E
2-8 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, November 97
♦ Link of limit values to relays
• Each limit value can be linked only once
• None or 1 to 6 limit values can be linked to one relay
• If a relay is linked to several limit values, thelimit value
exceedances can be combined in two ways:
a) AND
The relay trips, if all limit values that are linked to this
relay are exceeded.
b) OR
The relay trips, if at least one of the limit values
linked to this relay is exceeded.
• OK-Relay normally energized
• Alarm relays
3)
normally energized
K1, K2, K3 or normally de-energized latching or non-latching
• Alarm delay Time
3)
can be set individually for each limit value from
between 1 and 99 s (accuracy ± 5 %
• Reset function 1 galvanically free contact switch to reset
latched relays.
♦ Remote Interface Number of Ports 2 Interface Type RS-232-C (EIA),
(Data only)
• Baud rate
3)
1200, 2400, 4800 or 9600 Parity none Data Bits 8
Stop Bits 1
3) The respective selection is made software-controlled in dialog mode.