List of Setup Parameters VC 1100
Version 2 → parqalist/VC1100E
5-28 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98
Comments to item 2:
In the latching mode, a relay remains latched until VIBROCON-
TROL 1100 receives a reset command. In the non-latching mode,
VIBROCONTROL 1100 resets the relays automatically when the
monitored signal drops below the limit value.
Comments to item 3:
The following table shows the contact positions for normally de-
energized and normally energized relay operating modes.
Mode No alarm Alarm
Normally de-energized
Normally energized
Relay active
Relay not active
Relay not active
Relay active
Comments to item 4:
If several alarm limits control one relay, combine the alarms using
a logical AND or a logical OR.
N 01 Channel A : lim_1 controls relay ...
Choises : --, K1, K2, K3
Function : Assign event "lim_1A exceeded" to a relay
-- = lim_1A does not control a relay
K1 = lim_1A controls relay K1
K2 = lim_1A controls relay K2
K3 = lim_1A controls relay K3
N 02 Channel B : lim_1 controls relay ...
Choises : --, K1, K2, K3
Function : Assign event "lim_1B exceeded" to a relay
-- = lim_1B does not control a relay
K1 = lim_1B controls relay K1
K2 = lim_1B controls relay K2
K3 = lim_1B controls relay K3