EasyManua.ls Logo

schmersal PSC1 - Parameter Configuration; Function Check; Validation

schmersal PSC1
201 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation manual
HB-37420-810-01-25F-EN PSC1-C-100 Installation manual - V2.2.docx Page 161 of 201
Version: 25F
7.5 Parameter configuration
The parameters are configured using the program SafePLC2. To be able to send the data to the
module, a programming adapter is required; the user must install the driver for this adapter prior
to use.
For a description of the parameter configuration, see Programming manual
7.6 Function check
To safeguard the safety of the module, a function test on the safety functions must be
undertaken once per year by the user.
For this purpose, the blocks (inputs, outputs, monitoring functions and logic blocks) used in the
parameter configuration must be tested in relation to their function and shutdown, see the
Programming manual.
7.7 Validation
To safeguard the safety functions implemented, the parameters and operators must be checked
and documented by the user after completion of commissioning and parameter configuration.
Support for this task is provided by the validation wizard in the user interface (see section
"Safety-related check").

Table of Contents

Related product manuals