8021823/126P/2018-12-17 • © SICK AG • Subject to change without notice 91
PROFINET IO-interface
Module parameter "MF2"
Name Description
MF2 Function Select function for the output MF2.
Value range
[Output] Distance Threshold: Output switches when the
distance from module parameter "[MF2 Distance]
Threshold" was undercut.
[Output] Speed Threshold: Output switches when the speed
from module parameter "[MF2 Distance] Speed" was
exceeded. The direction is determined in the module
parameter "[MF2 Speed] mode".
[Output] Service: The output switches when at least one of
the service bits activated was set.
Standard value
[Output] Service
[MF2] Active
State
Select switching level for input and output MF2.
Value range
Low
High
Standard value
Low
[MF2 Distance]
Threshold [mm]
Enter value of the distance threshold in "mm".
Value range
–300,000 ... 300,000 mm
Standard value
1,990 mm
[MF2 Distance]
Hysteresis [mm]
Enter hysteresis of the distance threshold in "mm".
Value range
1 ... 300,000 mm
Standard value
10 mm
[MF2 Speed]
Threshold
Enter speed threshold.
Value range
0 ... 15,000 mm/s
Standard value
5,000 mm/s
[MF2 Speed]
Mode
Select direction for detection in which the speed is exceeded.
Value range
Negative direction [–]
Positivedirection[+]
Bothdirections[+/–]
Standard value
Bothdirections[+/–]