Connections 05.05
6-14 Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
6.1.2.4 List of recommended RI suppression filters made by EPCOS:
Rated current
RI suppression
filter (A)
RI suppression filter
Order number
Terminal
cross-section
(mm²)
Holes for M . .
Weight
(kg)
Dimensions
HxWxD
(mm)
8 B84143-G8-R11* 4 mm² 1,3 80 x 230 x 50
20 B84143-G20-R11* 4 mm² 1,3 80 x 230 x 50
36 B84143-G36-R11* 6 mm² 2,8 150 x 280 x 60
50 B84143-G50-R11* 16 mm² 3,3 150 x 60 x 330
66 B84143-G66-R11* 25 mm² 4,4 150 x 330 x 80
90 B84143-G90-R11* 25 mm² 4,9 150 x 330 x 80
120 B84143-G120-R11* 50 mm² 7,5 200 x 380 x 90
150 B84143-G150-R11* 50 mm² 8,0 200 x 380 x 90
220 B84143-G220-R11* 95 mm² 11,5 220 x 430 x 110
150 B84143-B150-S** M10 13 140 x 310 x 170
180 B84143-B180-S** M10 13 140 x 310 x 170
250 B84143-B250-S** M10 15 115 x 360 x 190
320 B84143-B320-S** M10 21 115 x 360 x 260
400 B84143-B400-S** M10 21 115 x 360 x 260
600 B84143-B600-S** M10 22 115 x 410 x 260
1000 B84143-B1000-S** M12 28 165 x 420 x 300
1600 B84143-B1600-S** 2 x M12 34 165 x 550 x 300
2500 B84143-B2500-S** 4 x M12 105 200 x 810 x 385
*) The code for the construction type must be inserted instead of *:
0 = 480 V 2 = 530 V
**) The code for the construction type must be inserted instead of **:
20 = 500 V 21 = 760 V 24 = 690 V
*) RI suppression filters produce discharge currents. VDE 0160 stipulates a 10 mm² PE
connection. To ensure an optimum filtering effect, it is absolutely essential to mount the filters and
converter on a single metal plate.
In the case of converters with a 3-phase connection, the minimum rated current of the filter
equals the output DC of the converter times 0.82.
With a two-phase connection (field supply and electronics supply), only two phases are connected
to the three-phase RI suppression filter. In this case, the line current equals the field DC (plus 1A
for the electronics supply).
Important technical data of Siemens RI suppression filters:
Rated supply voltage 3AC 380-460 V (± 15%)
Rated frequency 50/60 Hz (± 6%)
Operating temperature
0° C to +40° C
Degree of protection IP20 (EN60529) IP00 with 500 A and above
For further technical data about RI suppression filters, please refer to the Operating Instructions:
SIMOVERT Master Drives RI Suppression Filters EMC Filters, Order number:
6SE7087-6CX87-0FB0.