Function diagrams 05.05
8-28 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Sheet G140 Brake control
0
T
8
7
564321
Q
SET
(Q=1)
RESET
(Q=0)
Q
0T
1
2
1
1
1
1
&
&
- G140 -
[G182.6]
[G187.6]
[G180.6]
B0255
B0250
B0104
P080
B0164
Footnote 1:
The signal "automatic restart" is generated by the sequence control.
If the voltage at the power section fails briefly in the "operating" state (see P086)
(and if automatic restart is selected, i.e. P086 > 0), the "operating" signal goes to log. "0" and
the "automatic restart" signal to log. "1" during this time.
This causes the brake to remain open during this short time without torque.
Footnote 2:
A negative value in P087 means that the signal "Open brake" is delayed with respect to the enable
for the firing pulses for the thyristor. Only this case is shown in this function diagram.
Brake control
Brake opening time
P088 (0.00)
(0.00...10.00 s)
Delayed firing pulse disable
Close brake
Open brake
Priority:
1. RESET
2. SET
Firing pulse disable
(1 = firing pulse disabled)
Automatic restart
(see footnote 1)
OFF1 or OFF3
from the sequence control
Operation
1 = n<n
min
P087 (0.00)
(-10.00...0.00 s)
[see footnote 2]
from control word 1