Function diagrams 05.05
8-50 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Sheet G182 Status word 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
321Bit0
4567
Bit8
910
111213
14
15
8
7
564321
- G182 -
[G187.6]
[G187.6]
[G136.7]
[G188.3]
[G170.6][G171.6]
[G172.6][G173.6]
[G174.6][Z110.6]
[G136.1][G136.3][G140.2]
[G117.5][G166.1]
[G160.1][G160.2]
r652
K0032
B0100
B0101
B0102
B0103
B0104
B0105
B0106
B0107
B0108
B0109
B0110
B0111
B0112
B0113
B0114
B0115
B0116
B0117
B0120
B0121
B0122
B0123
B0124
B0125
B0126
B0127
B0128
B0129
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Status word 1
Meaning
Status word 1
1 = Ready to switch on
0 = Not ready to switch on
1 = Ready to operate (pulses disabled)
0 = Not ready to operate
1 = Run (output terminals energized)
0 = Pulses disabled
1 = Fault is active (pulses disabled)
0 = No fault is active
0 = OFF2 applied
1 = No OFF2 applied
0 = OFF3 applied
1 = No OFF3 applied
1 = Switch-on inhibit
0 = No switch-on inhibit (converter can be switched on)
1 = Alarm is active
0 = No alarm is active
0 = Setpoint/actual value deviation detected
1 = No setpoint/actual value deviation detected
1 = PZD control requests (always 1)
1 = Undervoltage fault (F006)
0 = No undervoltage fault is active
1 = Request to energize main contactor
0 = Request not to energize main contactor
1 = Ramp-function generator active
0 = Ramp-function generator not active
1 = Positive speed setpoint
0 = Negative speed setpoint
Spare
from sequencing control
from sheet "Signals (1)"
from alarm processing
from fault processing
from fault processing
from sheet "Signals (1)"
from sheet "Signals (2)"
from sequencing control
from sequencing control
rom sequencing control
from sequencing control
from sequencing control
from sequencing control
from ramp-function generator
Bit No.
Display of status word 1 (r652)
on 7-segment display
1=Actual value
≥
comparison setpoint (P373)
0=Actual value < comparison setpoint (P373)
from relay output line contactor