Parameter list 05.05
11-98 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
11.51 Resetting and storing parameters,
list of existing and modified P and r parameters
P970
*
Restore factory setting
Reset parameters to factory setting (default)
0: Parameter reset: All parameters are reset to their original values
(factory setting). This parameter is then automatically reset to 1.
1: No parameter reset
Note: Function can also be selected by setting P051=21.
0 to 1
1
Ind: None
FS=1
Type: O2
P052 = 3
P051 = 40
Offline
P971
*
EEPROM transfer
Transfer of parameter values from RAM to EERPROM on switchover from 0
to 1.
It takes approximately 15s to process all values. The PMU remains in value
mode for this period.
0 to 1
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
r980 List of existing parameter numbers, start
Visualization parameter for displaying the first 100 parameter numbers in
the P or r parameter range (0 to 999). The parameter numbers are listed in
ascending sequence.
Repetition of a number over several indices means that there are no further
parameter numbers in the 0 to 999 range.
The list is continued at the parameter whose number is displayed under
index 101.
See also r989
Ind: 101
Type: O2
P052 = 3
r981 List of existing parameter numbers, continuation
See r980.
Ind: 101
Type: O2
P052 = 3
r982 List of existing parameter numbers, continuation
See r980.
Ind: 101
Type: O2
P052 = 3
r983 List of existing parameter numbers, continuation
See r980.
Ind: 101
Type: O2
P052 = 3
r984 List of existing parameter numbers, continuation
See r980.
Ind: 101
Type: O2
P052 = 3
r985 List of existing parameter numbers, continuation
See r980.
Ind: 101
Type: O2
P052 = 3
r986 List of existing parameter numbers, continuation
See r980.
Ind: 101
Type: O2
P052 = 3
r987 List of existing parameter numbers, continuation
See r980.
Ind: 101
Type: O2
P052 = 3
r988 List of existing parameter numbers, continuation
See r980.
Ind: 101
Type: O2
P052 = 3
r989 List of existing parameter numbers, continuation
Continuation of the list can be found under index 101. Please note:
860 = r860 (TECH BOARD installed)
2980 = n980
See also r980.
Ind: 101
Type: O2
P052 = 3
r990 List of modified parameter numbers, start
Visualization parameter for displaying the first 100 modified parameters in
the P or r parameter range (0 to 999). The parameter numbers are listed in
ascending sequence.
Repetition of a number over several indices means that there are no further
modified parameters in the 0 to 999 range.
The list is continued at the parameter whose number is displayed under
index 101.
See also r999.
Ind: 101
Type: O2
P052 = 3
r991 List of modified parameter numbers, continuation
See r990.
Ind: 101
Type: O2
P052 = 3