EasyManua.ls Logo

Siemens 7UT51

Siemens 7UT51
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Binary-Signal Inputs, Signal Contacts, Trip Contacts, and LED Indicators
7UT51 v3
124 PRIM-2330C
Figure 13.2
Signal Contacts
Figure 13.3
LED Targets
Each signal contact is controlled
by up to 20 events.
For example:
0141 Failure of internal 24V power supply
0511 General trip of the relay
1566 49-Thermal O/L prot.1: Thermal warn.
1571 49-Trip by thermal O/L protection 1
5671 87-Diff protection: General Trip
5821 Restricted Ground Fault: General Trip
5921 Transformer tank prot: General trip
Use to...
Sound alarms for operators
Signal other protection devices
Signal Contacts
Event 1
Event 2
:
:
Event 20
Make Capacity: 20 W/VA
Break Capacity: 20 W/VA
Switching Voltage: 250 V
Permissible Current: 1 A
Configurable
7UT512: 4 0
7UT513: 5 5
Self-Test Alarm: 1
Each LED is controlled by up to 20 events.
For example:
95 Parameters are Being Set
163 Failure: Current Symmetry Supervision
501 General Fault Detection
1566 Thermal Overload 1 Warning Stage
1571 Trip by Thermal Overload Protection 1
4533 External Trip 1 is Active
5616 87 Function is Blocked
5621 87 Time Delay Started
5641 87 Function Blocked by Harmonics
5651 87 Blocked by Saturation on Phase A
5817 87N Time Delay Started
Each event can either latch (“memorized”),
or not latch (“not memorized”) an LED.
Latched LEDs can be reset using a key on
the front panel, a binary-signal input, or an
attached PC running WinDIGSI.
LED Targets
Event 1
Event 2
:
:
Event 20
Power: 1
Blocked: 1
Configurable
7UT512: 6
7UT513: 14

Table of Contents

Related product manuals