EasyManua.ls Logo

Siemens 7UT51

Siemens 7UT51
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7UT51 v3
Binary-Signal Inputs, Signal Contacts, Trip Contacts, and LED Indicators
13
PRIM-2330C 125
Figure 13.4
Trip Contacts
Figure 13.5
Trip Contact Monitoring Circuit
Each signal contact is controlled
by up to 20 events.
For example:
0511 General Trip of the Relay
1571 49-1 Thermal Overload Trip
1621 49-2 Thermal Overload Trip
2451 Backup Overcurrent Trip
4537 External Event 1 Trip
5673 87 Diff Trip Phase B
5691 87 Diff Trip
5821 87N RGF Trip
5921 64T Tank Trip
Use to...
Trip circuit breakers
Trip Contacts
7UT512: 2 0
7UT513: 3 2
Make Capacity: 1000 W/VA
Break Capacity: 30 W/VA
Switching Voltage: 250 V
Permissible Current: 5 A continuous
30 A for 0.5 s
Event 1
Event 2
:
:
Event 20
Trip
Contact
Trip Relay
Coil
TR
T1
T2
TCML
To second Trip Contact
TCML:
Trip Circuit Monitoring Logic
Constant current source
with Field effect Transistors
One Trip Contact is controlled by two
Transistors (T1 & T2)
For a pair of Trip Contacts, there is an
additional Release Transistor (TR)
During normal operation, a trip contact is
inactive. If all Transistors are healthy (high
resistance), a low current will flow over the
opto-coupler Diodes and the Trip-contact-coil.
If a Transistor is switched on, the opto-coupler
will be inactive.
Sequentially, each Transistor can be switched
on and off, to test the status of the transistor
and the opto-coupler
In case of Trip-command, all Transistors are
switched on.
The status of the Trip Transistors and the trip
coil is monitored continuously.

Table of Contents

Related product manuals