7UT51 v3
Settings Record
20
PRIM-2330C 225
7226
REAR PARITY
Parity and stop
-
bits for the rear port
VDEW/WinDIGSI/LSA X
NO PARITY,2 STOP
NO PARITY,1 STOP
7235
PROGviaREAR
Programming via the rear port
NO X
YES
7400
WAVEFORM CAPTURE
Password level = 3
7402
WAVE TRIG.
Trigger for waveform capture
TRIG WITH PICKUP X
TRG PU/SAVE TRIP
TRIG WITH TRIP
7410
MAX LENGTH
Max length of a waveform capture record
0.30
-
5.00 s 1.00 s
7411
PRETRIG.
Amount of captured waveform prior to trigger
0.05
-
0.50 s 0.10 s
7412
POSTTRIG.
Amount of captured waveform after trigger
0.05
-
0.50 s 0.10 s
7431
DI CaptTime
Discrete input initiated waveform capture time
0.10
-
5.00 s or 0.50 s
7432
KeyCaptTime
Keyboard initiated waveform capture duration
0.10
-
5.00 s 0.50 s
7490
LSA LENGTH
Length of fault log (for previous LSA)
Fixed 660 Samples X
Varbl Wave<=3k samp.
7800
DEVICE OPTIONS
Password level = 3
7801
PROT. OBJ.
Selection of the protected object
2
-
winding trans X
3
-
winding trans
Motor/Generator
Two line tie point
three line tie point
1ph
-
transformer
7806
STAR
-
POINT A
Selection of transformer A star point
No assignment X
Side 1
Side 2
Side 3/Virt. obj.
7807
STAR
-
POINT B
Selection of transformer B star point
No assignment X
Side 1
Side 2
Side 3/Virt. obj.
7816
87 STATUS
87
-
State of the differential protection
EXISTENT X
NONEXISTENT
7819
RGF PROT.
Restricted ground
-
fault protection
NONEXISTENT X
Winding 1
Winding 2
Winding 3
Virtual object
7821
BACK
-
UP O/C
Backup overcurrent protection
NONEXISTENT X
Reference Side 1
Reference Side 2
Reference Side 3
Virtual object
7824
49 Therml1
49
-
Thermal overload protection 1
NONEXISTENT X
Reference Side 1
Reference Side 2
Reference Side 3
Virtual object
Addr
LCD Line 1
WinDIGSI Description
Options or
Range and Unit
Default Setting