© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–168
6210
Active Alarm Log Entry
25
Same as 5850 – 5864 except for entry 25
6225
Number of
unacknowledged
alarms in active alarm
log
— 1.0 0 – 50
The number of active alarms added to the active
alarm log since reset that have not been
acknowledged
6226
Number of
unacknowledged
alarms in active alarm
list
— 1.0 0 – 50
The number of alarms that have not been
acknowledged since reset
Alarm History Log
6250
Acknowledge/Relay/Pri
ority Entry 1
— —
Bits 0 -7 = Alarm Number
Bits 8-11 = Unused
Bits 12-13 = Priority
Bit 14 = relay (1 = association)
Bit 15 = Alarm Acknowledged
6251 Unique Identifier — — 0 – 0xFFFFFFFF
Bits 00 – 07 = Level (0 – 9)
Bits 08 – 15 = Alarm Type
Bits 16 – 31 = Test Register
6253 Label — — ASCII 16 Characters
6261
Extreme Value for
History Log Entry 1
A-F Units/Scale 0 – 32,767 Does not apply to digital or unary alarms
6262
Dropout Date/Time
Entry 1
—
Table A–1
on page 121
Table A–1
on page 121
6265
Elapsed Seconds for
History Log Entry 1
— Seconds 0 – 2147483647
6267
Alarm History Log
Entry 2
Same as 6250 – 6266 except for entry 2
6284
Alarm History Log
Entry 3
Same as 6250 – 6266 except for entry 3
6301
Alarm History Log
Entry 4
Same as 6250 – 6266 except for entry 4
6318
Alarm History Log
Entry 5
Same as 6250 – 6266 except for entry 5
6335
Alarm History Log
Entry 6
Same as 6250 – 6266 except for entry 6
6352
Alarm History Log
Entry 7
Same as 6250 – 6266 except for entry 7
6369
Alarm History Log
Entry 8
Same as 6250 – 6266 except for entry 8
6386
Alarm History Log
Entry 9
Same as 6250 – 6266 except for entry 9
6403
Alarm History Log
Entry 10
Same as 6250 – 6266 except for entry 10
6420
Alarm History Log
Entry 11
Same as 6250 – 6266 except for entry 11
Table A–5: Registers for Alarm Logs
Reg Name Scale Units Range Notes