ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–170
Table A–6: Registers for Alarm Position Counters
Reg Name Scale Units Range Notes
Alarms
Alarms — System Status
10011 Active Alarm Map — Binary
0x0000 –
0xFFFF
0 = Inactive, 1 = Active
Bit00 = Alarm #01
Bit01 = Alarm #02 …… etc.
10023 Active Alarm Status — Binary
0x0000 –
0x000F
Bit00 = 1 if any priority 1-3 alarm is active
Bit01 = 1 if a “High” (1) priority alarm is active
Bit02 = 1 if a “Medium” (2) priority alarm is active
Bit03 = 1 if a “Low” (3) priority alarm is active
10024
Latched Active Alarm
Status
—Binary
0x0000 –
0x000F
Latched Active Alarms:
(from the last time the register was cleared)
Bit00 = 1 if any priority 1-3 alarm is active
Bit01 = 1 if a “High” (1) priority alarm is active
Bit02 = 1 if a “Medium” (2) priority alarm is active
Bit03 = 1 if a “Low” (3) priority alarm is active
10025 Total Counter — 1.0 0 – 32,767
Total alarm counter, including all priorities 1, 2 and
3
10026 P3 Counter — 1.0 0 – 32,767 Low alarm counter, all priority 3s
10027 P2 Counter — 1.0 0 – 32,767 Medium alarm counter, all priority 2s
10028 P1 Counter — 1.0 0 – 32,767 High alarm counter, all priority 1s
10029 Pickup Mode Selection — Binary 0x0 – 0xFFFF
Selection of absolute or relative pickup test for each
of the alarm positions (if applicable, based on type)
Alarm #01 is least significant bit in register 10040
0 = Absolute (default)
1 = Relative
Bit00 = Alarm #01
Bit01 = Alarm #02, etc.
10041
Number Of Samples In
Relative Threshold
Average
— 1.0 5 – 30
Number of 1-second update intervals used to
compute the RMS average value used in relative
pickup alarms
(Default = 30)
Alarms — Counters
10115
Alarm Position #001
Counter
— 1.0 0 – 32,767 Standard Speed Alarm Position #001
10116
Alarm Position #002
Counter
— 1.0 0 – 32,767 Standard Speed Alarm Position #002
10117
Alarm Position #003
Counter
— 1.0 0 – 32,767 Standard Speed Alarm Position #003