ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Chapter 4—Metering Capabilities 2/2008
EN–58
“Setting Up Individual Harmonic Calculations” on page 216 for
information on how to configure harmonic calculations.
Table 4–6: Power Analysis Values
Value Reportable Range
THD—Voltage, Current
3-phase, per-phase, neutral 0 to 3,276.7%
thd—Voltage, Current
3-phase, per-phase, neutral 0 to 3,276.7%
Fundamental Voltages (per phase)
Magnitude
Angle
0 to 1,200 kV
0.0 to 359.9°
Fundamental Currents (per phase)
Magnitude
Angle
0 to 32,767 A
0.0 to 359.9°
Miscellaneous
Displacement P.F. (per phase, 3-phase) –0.002 to 1.000 to +0.002
Phase Rotation ABC or CBA
Unbalance (current and voltage) ➀ 0.0 to 100.0%
Individual Current and Voltage Harmonic Magnitudes ➁ 0 to 327.67%
Individual Current and Voltage Harmonic Angles ➁ 0.0° to 359.9°
➀ Readings are obtained only through communications.
➁
Current and Voltage Harmonic Magnitude and Angles 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, and 13 are shown on the
display.