EasyManua.ls Logo

Siemens ACCESS 9340 - Page 93

Siemens ACCESS 9340
264 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved.
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Chapter 6—Basic Alarms
EN–85
Digital
060 Digital Input On
The digital input transition alarms will occur whenever the digital input
changes from off to on. The alarm will dropout when the digital input
changes back to off from on. The pickup and dropout setpoints and
delays do not apply.
061 Digital Input Off
The digital input transition alarms will occur whenever the digital input
changes from on to off.The alarm will dropout when the digital input
changes back to on from off. The pickup and dropout setpoints and
delays do not apply.
070 Unary
This is a internal signal from the meter and can be used, for example, to
alarm at the end of an interval or when the meter is reset. Neither the
pickup and dropout delays nor the setpoints apply.
Table 65: Alarm Types
Type Description Operation
Table 6–5: Default Alarm Configuration - Factory-enabled Alarms
Alarm
No.
Standard Alarm
Pickup
Limit
Pickup
Limit Time
Delay
Dropout
Limit
Dropout
Limit Time
Delay
19 Voltage Unbalance L-N 20 (2.0%) 300 20 (2.0%) 300
20 Max. Voltage Unbalance L-L 20 (2.0%) 300 20 (2.0%) 300
53
End of Incremental Energy
Interval
00 0 0

Table of Contents

Related product manuals