I/O device digital inputs/digital outputs
9.3 I/O device digital inputs/digital outputs
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
151
Total current of the outputs
• All mounting positions to 60°C
Max. 3.9 A per 1L+ and 2L+
Digital inputs/digital outputs
Number of configurable inputs/outputs 8
Number of inputs that can be controlled simulta-
8, in all mounting positions
• Ethernet interface
1500 V
rms
(IEEE802.3)
• All other circuit elements
707 V DC (type test)
• Between 1L+ and 2L+
Yes
• Between 1L+, channels and all other circuit
elements
No
• Between channels
No
• Between Ethernet and all other circuit ele-
ments
Yes
Status, interrupts, diagnostics
• Group error/maintenance
Red/yellow "SF/MT" LED
• Bus monitoring PROFINET IO
Red "BF" LED
• Monitoring of supply voltage 1L+
Green "ON" LED
• Existing connection to network
Green "P1 LK" and "P2 LK" LED; LED for
PROFINET IO infeed and loop-through
• Digital input
Green LED
• Fault at digital input
Red LED
• Digital output
Green LED
• Fault at digital output
Red LED
• Diagnostic information can be read
Yes
• Failure of 1L+ and 2L+
Yes
• Sensor supply short-circuit
Yes, per channel
• Digital output short-circuit
Yes, per channel
• Digital input wire break
Yes, input current < 0.3 mA, per channel
• Digital output wire break
Yes, in the off state, per channel