EasyManua.ls Logo

Siemens SIMATIC ET 200pro - Setpoints; Overview

Siemens SIMATIC ET 200pro
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting functions
8.3 Setpoints
SIMATIC ET 200pro FC-2 converter
102 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
The abbreviations S1 … S5b to identify the converter states are defined in the PROFIdrive
profile.
Converter
status
Explanation
S1 In this state, the converter does not respond to the ON command. The converter
goes into this state under the following conditions:
• ON was active when switching on the converter.
Exception: When the automatic start function is active, ON must be active after
switching on the power supply.
• OFF2 or OFF3 is selected.
S2
This state is required to switch on the motor.
S3
The converter waits for the operating enable.
S4 The motor is switched on.
S51 The motor was switched off with OFF1 and brakes with the ramp-down time of the
ramp-function generator.
S52 The motor was switched off with OFF3 and brakes with the OFF3 ramp-down time,
or at the current limit.
8.3
Setpoints
8.3.1
Overview
The inverter receives its main setpoint from the setpoint source. The main setpoint generally
specifies the motor speed.
Figure 8-3 Setpoint sources for the inverter

Table of Contents

Other manuals for Siemens SIMATIC ET 200pro

Related product manuals