EasyManua.ls Logo

Siemens SIMATIC ET 200pro - Alarms

Siemens SIMATIC ET 200pro
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Alarms, faults and system messages
11.4 Alarms
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
205
Designation
Format
Example for the
content
Valid for
PROFINET
Valid for
PROFIBUS
ORDER_ID Visible String
[20]
6SL3246-0BA22-
1FA0“
SERIAL_NUMBER Visible String
[16]
„T-R32015957
HARDWARE_REVISION
u16
0001 hex
SOFTWARE_REVISION
char, u8[3]
„V“ 04.70.19
REVISION_COUNTER
u16
0000 hex
PROFILE_ID
u16
3A00 hex
PROFILE_SPECIFIC_TYPE
u16
0000 hex
IM_VERSION
u8[2]
01.02
IM_SUPPORTED
bit[16]
001E hex
11.4
Alarms
Alarms have the following properties:
They do not have a direct effect in the converter and disappear once the cause has been
removed
They do not need have to be acknowledged
They are signaled as follows
Status display via bit 7 in status word 1 (r0052)
At the Operator Panel with a Axxxxx
Via STARTER, if you click on TAB
at the bottom left of the STARTER screen
In order to pinpoint the cause of an alarm, there is a unique alarm code and also a value for
each alarm.
Alarm buffer
For each incoming alarm, the converter saves the alarm, alarm value and the time that the
alarm was received.
Figure 11-2 Saving the first alarm in the alarm buffer
r2124 and r2134 contain the alarm value - important for diagnostics - as "fixed point" or
"floating point" number.
The alarm times are displayed in r2145 and r2146 (in complete days) as well as in r2123 and
r2125 (in milliseconds referred to the day of the alarm).

Table of Contents

Other manuals for Siemens SIMATIC ET 200pro

Related product manuals