SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
219
Technical data
12
12.1
Technical data
Technical data
General technical data and information about the mechanical and climatic environmental
condition of the ET 200pro system is provided in the "SIMATIC ET 200pro Distributed I/O
System" manual.
Note
Deviating from this general technical data, for the ET
200pro FC--2 inverter, the following
applies:
Drop test (in original package)
≤ 0.35 m.
Table 12- 1 Technical data
Date
Unit
Value
Rated input voltage
V
AC 400
Permissible voltage range min.
V
AC 380
Permissible voltage range max.
V
AC 480
Rated output current
@ 45 °C
A
3,9
@ 55 °C
A
3,5
Maximum output current (3 s)
A
2 x rated output current
Rated input current 3AC
A
3,7
Integrated device fuse
A
16, medium time-lag
Rated power @ 55 °C
kW
1,10
Power with overload (150% for 60 s every 300 s)
kW
1,65
Power with overload (200% for 3 s every 300 s)
kW
2,20
Power without overload capability kW 1,20
Integrated brake control
V DC 200
Pulse frequency (factory setting)
kHz
4
Installation altitude
above sea level m 2000
Efficiency η
%
95 … 97
Power factor
---
0,9
Mechanical data
Width
mm
155