Alarms, faults and system messages
11.6 List of alarms and faults
SIMATIC ET 200pro FC-2 converter
218 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
F30036 Overtemperature, inside area
•
Check the fan filter elements.
• Check whether the ambient temperature is in the permissible range.
F30037 Rectifier overtemperature See F30035 and, in addition:
• Check the motor load.
• Check the line phases
Check the internal fan and if required replace.
F30059 Internal fan defective Check the internal fan and if required replace.
A30502 DC link overvoltage
• Check the unit supply voltage (p0210).
• Check the dimensioning of the line reactor.
A30920 Temperature sensor fault Check that the sensor is connected correctly.
For further information, please refer to the List Manual.