EasyManua.ls Logo

Siemens SIMATIC ET 200pro - Mounting the Racks

Siemens SIMATIC ET 200pro
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
4.2 Mounting the racks
SIMATIC ET 200pro FC-2 converter
30 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Maximum size
The width of an ET 200pro is limited mechanically and electrically.
Table 4- 1 Mechanical limits
Features
Rule
Number of mod-
ules
16
Width
1 m (without rack)
Number of invert-
ers
5
Table 4- 2 Electrical limits
ET 200pro features
Inverter features
Rule
Load capacity of the electronics supply 1L+
5 A
Power consumption at 1L+
0.8 A per inverter
Load capacity of the load voltage supply 2L+
10 A
Power consumption at 2L+ The load caused by the frequency inverter
is negligible.
Current carrying capacity of the power supply
25 A
Power consumption at the
power supply
The inverters power consumption depends
on the connected motor.
4.2
Mounting the racks
The frequency converter is mounted on the wide rack. The following versions are possible:
Rack, wide
Rack, compact-wide

Table of Contents