Setting functions
8.5 Motor control
SIMATIC ET 200pro FC-2 converter
118 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Additional information on U/f characteristics can be found in the parameter list and in the
function diagrams 6300 ff of the List Manual.
8.5.1.3
Optimizing motor starting
Setting the voltage boost for U/f control
After selection of the V/f characteristic, no further settings are required in most applications.
In the following circumstances, the motor cannot accelerate to its speed setpoint after it has
been switched on:
Load moment of inertia too high
Load torque too large
Ramp-up time p1120 too short
To improve the starting behavior of the
motor, the V/f characteristic can be
raised at low speeds.
The inverter raises the voltage in a
c-
cordance with the starting currents
p1310
p1312.
The adjacent diagram shows the resul
t-
ing voltage boost u
sing a linear charac-
teristic as an example.
Requirements
Set the ramp-up time of the ramp-function generator to a value 1 s (< 1 kW) 10 s
(> 10 kW), depending on the power rating of the motor .
Increase the starting current in steps of 5 %. Excessively high values in p1310 ... p1312
can cause the motor to overheat and switch off (trip) the inverter due to overcurrent.
If the message A07409 appears, you must not increase any of the parameters.
Procedure
Proceed as follows to set the voltage boost:
1. Switch off the motor with a setpoint of just a few revolutions per minute.
2. Check whether the motor rotates smoothly.
3. If the motor rotates eccentrically or even stops, increase the voltage boost p1310 until the
motor rotates smoothly.
4. Accelerate the motor to the maximum speed with maximum load.