Setting functions
8.5 Motor control
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
119
5. Check whether the motor is following the setpoint.
6. If necessary, increase the voltage boost p1311 until the motor accelerates without
problem.
In applications with a high break loose torque, you must additionally set parameter p1312
higher to achieve a satisfactory response.
You have set the voltage boost.
p1310
Starting current (voltage boost) permanent
(factory setting 50 %)
Compensates for voltage drops caused by long motor cables and the ohmic losses in
p1311
Starting current (voltage boost) when accelerating
(factory setting 0 %)
Provides additional torque when the motor accelerates.
p1312
Starting current (voltage boost) when starting
(factory setting 0 %)
Provides additional torque, however, only when the motor accelerates for the first time
after it has been switched on ("break loose torque").
You will find more information on this function in the parameter list and in function diagram
6301 in the List Manual.