Configure the fieldbus
7.1 PROFIdrive profile for PROFIBUS and PROFINET
SIMATIC ET 200pro FC-2 converter
88 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Status word 1 (bits 0-10 in accordance with PROFIdrive profile, bits 11-15 specific to the
inverter).
Signal interconnec-
tion in the inverter
Power supply switched on; electronics initialized; pulses locked.
1 1 = Ready Motor is switched on (ON/OFF1 = 1), no fault is active. With the com-
mand "Enable operation" (STW1.3), the inverter switches on the motor.
p2080[1] = r0899.1
2 1 = Operation ena-
Motor follows setpoint. See control word 1, bit 3. p2080[2] = r0899.2
The inverter has a fault. Acknowledge fault using STW1.7.
Coast down to standstill is not active.
Quick stop is not active.
6 1 = Closing lockout
It is only possible to switch on the motor after an OFF1 followed by ON. p2080[6] = r0899.6
Motor remains switched on; no acknowledgment is necessary.
8 1 = Speed deviation
within the tolerance
Setpoint / actual value deviation within the tolerance range. p2080[8] = r2197.7
9 1 = Master control
The automation system is requested to accept the inverter control. p2080[9] = r0899.9
10 1 = Comparison
speed reached or
Speed is greater than or equal to the corresponding maximum speed. p2080[10] =
r2199.1
11 0 = I, M or P limit
Comparison value for current, torque or power has been reached or
p2080[11] =
12 1 = Holding brake
open
Signal to open and close a motor holding brake. p2080[12] =
r0899.12
13 0 = Alarm, motor
--- p2080[13] =
14 1 = Motor rotates
Internal inverter actual value > 0 p2080[14] =
r2197.3
0 = Motor rotates
Internal inverter actual value < 0
15 0 = Alarm, inverter
--- p2080[15] =
The converter interconnects the corresponding signals with the fieldbus interface. Generally,
the interconnections are protected so that they cannot be changed. With the appropriate
converter settings, these interconnections can be changed.
The telegram can be extended, by "attaching" additional signals.