Appendix
A.5 Acceptance tests for the safety functions
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
245
• The inverter signals neither faults nor alarms of the safety
functions (r0945[0…7], r2122[0…7]).
• The inverter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
4.
4.2.
• STO is not active (r9773.1 = 0).
• The inverter signals neither faults nor alarms of the safety
functions (r0945[0…7], r2122[0…7]).
You have performed the acceptance test of the STO function.
Machine documentation
Machine or plant description
Block diagram of the machine and/or plant:
…
…
…
…
…
…
Table A- 5 Hardware version of the safety-related inverter
Article number and hardware version of the inverter